DeviceNet Data Tables B-9
Instance 6 Attributes (Basic Device Configuration Data Read)
Assembly Structure
Common Services
Attribute
ID
Access
Rule
Name
DeviceNet
Data Type
3
Get
Data
Structure of
40 bytes (20 Words)
Param #
Parameter name
Data type
#bytes
Master Module Range
Default
Setting
Word No.
1
Present unit password
Int
2
PM-II will always return –1
0
1
2
New password
Int
2
PM-II will always return –1
0
2
3
Voltage mode
Int
2
0 = Demo
1 = Single
2 = Open Delta
3 = 3-Wire Delta
4 = 4-Wire Wye
5 = Direct Delta
4
3
4
Vaux voltage mode
Int
2
0 = AC
1 = DC
0
4
5
L1/L1/L3 PT primary
Float
4
1.0 to 10,000,000.0
120.0
5
6
6
L1/L2/L3 PT secondary
Float
4
1.0 to 999.0
120.0
7
8
7
I1/I2/I3 CT primary
Float
4
1.0 to 10,000,000.0
1 or 5
(1)
9
10
8
I1/I2/I3 CT secondary
Float
4
1.0 to 999.0
1 or 5
a
11
12
9
I4 CT primary
Float
4
1.0 to 10,000,000.0
1 or 5
a
13
14
10
I4 CT secondary
Float
4
1.0 to 999.0
1 or 5
a
15
16
11
Vaux PT primary
Float
4
1.0 to 10,000,000.0
1.0
17
18
12
Vaux PT secondary
Float
4
1.0 to 999.0
1.0
19
20
(1) This value will be 1 for 1 Amp Master Module (Cat. No. 1403-MM01X) or 5 for a 5 Amp Master Module (Cat. No. 1403-MM05X)
Service
Code
Service Name
0Ehex
Get_Attributes_Single