Assembly structure common services – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual
Page 75

Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-45
Assembly Structure
Common Services
Param #
Parameter name
Data
type
#bytes
Master Module Range
Default
Setting
Word
No.
1
Password
Int
2
-1, 0 to 9999
Correct password is required to
configure/reconfigure harmonic Analysis
functionality, but not required to select
harmonic channel or data group to be read back
in the harmonic results data assembly. If the
user is only selecting harmonic result data to be
read, set password to –1.
0
1
2
Harmonic channel
to be read
Int
2
1 = L1 Voltage
2 = L1 Current
3 = L2 Voltage
4 = L2 Current
5 = L3 Voltage
6 = L3 Current
7 = L4 Current
2
3
Read % distortion,
magnitude, or phase
angle data
Int
2
Selects which type of data appears in Instance
39 through Instance 43 (% distortion of
harmonic, magnitude of harmonic, or phase
angle of harmonic). 0 = % distortion, 1 =
magnitude, 2 = phase angle.
3
4
Reserved
Int
2
Reserved for future enable/disable of all
harmonic calculations.
4
5
IEEE 519 max short
circuit current
Float
4
0.0 to 10,000,000.0
0
5
6
6
IEEE 519 max
demand/load
current
Float
4
0.0 to 10,000,000.0
0
7
8
Service
Code
Service Name
10
hex
Set_Attributes_Single