Instance 31 attributes (min/max log results), Assembly structure common services, Assembly structure – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual
Page 67

Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-37
Instance 30 Attributes (Read of Min/max configuration)
Assembly Structure
Common Services
Instance 31 Attributes (Min/Max log results)
Assembly Structure
Attribute ID Access
Rule
Name
DeviceNet Data Type
3
Get
Data
Structure of
10 bytes (2 Words)
Param #
Parameter name
Data type
#bytes
Master Module Range
Default
Setting
Word
No.
1
Enable/disable min/max log
Int
2
0 = Disable
1 = Enable
1
1
2
Timestamp of last min/max clear
Int x 4
8
Year
2
Month, Day
Hour, Minute
Seconds, Hundredths
Service
Code
Service Name
0Ehex
Get_Attributes_Single
Attribute ID Access
Rule
Name
DeviceNet Data Type
3
Get
Data
Structure of
34 bytes (17 Words)
Param #
Parameter name
Data type
#bytes
Master Module Range
Word No.
1
MIN value for parameter
Float
4
0.0 to 9999x10
1
2
2
MAX value for parameter
Float
4
0.0 to 9999x10
21
3
4
3
Timestamp when MIN occurred
Int x 4
8
Year
5
Month, Day
6
Hour, Minute
7
Seconds, Hundredths
8
4
Timestamp when MAX occurred
Int
2
Year
9
Month, Day
10
Hour, Minute
11
Seconds, Hundredths
12