Unit Configuration

Configure with the Display

The PowerMonitor 500 unit provides menu-based configuration (programming)

by using its front panel display. The programming menus let you select

parameters to edit, select digits within parameters, and increase or decrease the

value of each digit.

Place the unit in Programming mode by pressing Program/select (8) for about

2 seconds. The front panel displays the PASSWORD? menu page 0 in Editing

mode. Enter the correct password by using the Up and Down arrows (the default

password is 0) and press Program/select. The front panel then displays the

CHANGE PAS menu page 10.

Refer to the programming flow chart beginning on

page 26

for a view of the

organization of programming menus and sub-menus. Each page is identified with

a number. Menu page numbers end in zero, while sub-menu pages end in

1 through 9. For example, the Change Password page is menu 10. Likewise, the

Dmd page is menu 80, and the demand interval Time page is menu 82.

While you are programming the power monitor, the display items and control

buttons function one way when you are navigating between menu or sub-menu

pages, and another way when you are editing a menu page.