Rockwell Automation 1420 PowerMonitor 500 User Manual
Page 38

38
Rockwell Automation Publication 1420-UM001D-EN-P - September 2013
Chapter 4
Communication
2. Click the Communication tab and enter the path and method.
3. Click OK to complete message setup.
Implicit Messaging - Generic Ethernet Module Input Data Connection
The PowerMonitor 500 unit with EtherNet/IP communication supports Class 1
connections to its nine assembly instances. To set up a Class 1 connection to a
selected assembly instance with a Logix controller, follow these steps.
1. Open the controller program offline in the Logix Designer application (or
online in Program mode if you are using a ControlLogix controller).
2. In the I/O configuration tree, right-click the Ethernet communication
module (for example, 1756-EN2T), and choose New Module.
3. From the Communication pull-down menu, choose ETHERNET-
MODULE Generic Ethernet Module.
Path
Method
<Ethernet Module, Port (always 2 for Ethernet), Power Monitor IP Address>
CIP