Rockwell Automation 1420 PowerMonitor 500 User Manual
Page 54

54
Rockwell Automation Publication 1420-UM001D-EN-P - September 2013
Appendix A
PowerMonitor 500 Unit Data Tables
Total and Partial Energy Meters - EtherNet/IP Data Table
Table 21 - Table Properties
CIP Assembly Instance
107
No. of Elements
18
Length in Words
36
Data Type
REAL
Data Access
Read Only
Table 22 - Total and Partial Energy Meters - EtherNet/IP Data Table
Element
Length
(words)
Description / Units
Data Format
Notes
0
2
Total kWh+
REAL
Range 0.0 … 999,999.999
1
2
Total GWh+
REAL
Range 0 … 9,999,999
2
2
Total kVARh+
REAL
Range 0.0 … 999,999.999
3
2
Total GVARh+
REAL
Range 0 … 9,999,999
4
2
Total kWh-
REAL
Range 0.0 … 999,999.999
5
2
Total GWh-
REAL
Range 0 … 9,999,999
6
2
Total kVARh-
REAL
Range 0.0 … 999,999.999
7
2
Total GVARh-
REAL
Range 0 … 9,999,999
8
2
Partial kWh+
REAL
Range 0.0 … 999,999.999
9
2
Partial GWh+
REAL
Range 0 … 9,999,999
10
2
Partial kVARh+
REAL
Range 0.0 … 999,999.999
11
2
Partial GVARh+
REAL
Range 0 … 9,999,999
12
2
Partial kWh-
REAL
Range 0.0 … 999,999.999
13
2
Partial GWh-
REAL
Range 0 … 9,999,999
14
2
Partial kVARh-
REAL
Range 0.0 … 999,999.999
15
2
Partial kVARh-
REAL
Range 0 … 9,999,999
16
2
Hours counter
REAL
17
2
Minutes counter
REAL
Range 0 … 59