Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 39

Advertising
background image

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

39

Communication

Chapter 4

4. Enter the setup parameters as listed in this dialog box and explained in

Table 5

.

Table 5 - Module Properties Setup Parameters

Item

Choices

General Tab

Name

Required; must be IEC 1131-3 compliant

Description

Optional

Comm Format

Depends on selected Assembly Instance

(1)

Address/Host Name

IP Address

IP address of target PowerMonitor 500 unit

Host Name

Not applicable

Connection Parameters

Assembly Instance

Size

Comm Format

Data Table Description

Input (select one)

100

20

Input Data - SINT

Product Information

101

12

Input Data - REAL

Real-time Voltage and Current

102

18

Input Data - REAL

Real-time Power, PF, Frequency

103

12

Input Data - REAL

MAX Voltage and Current

104

17

Input Data - REAL

MAX Power, PF, Frequency

105

12

Input Data - REAL

Dmd Voltage and Current

106

17

Input Data - REAL

Dmd Power, PF, Frequency

107

18

Input Data - REAL

Energy Meters

108

2

Input Data - INT

Alarm and Output Status

Output

98

N/A

Inst. 98 used for Input Only connection

99

N/A

Inst. 99 used for Listen Only connection1

Configuration

3

0

Instance 3 is a placeholder only

Connection Tab

RPI

100 ms or greater

Inhibit Module

Optional - unchecked by default

Major Fault

Optional - unchecked by default

Unicast Connection

Optional - checked by default

(1) Use the Listen Only connection only when an Input Only connection exists with another controller.