Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 64

Advertising
background image

64

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

Appendix B

Technical Specifications

Voltage overloads

Continuous 1.2

Un

For 500 ms

2 Un

Input impedance

400VL-L (V2)

> 1.6 M

208VL-L (V1)

> 1.6 M

5(6)A

< 0.2 VA

Frequency 40…440

Hz

Table 33 - Input Specifications

Attribute

Value

Table 34 - Pulse (digital) Output Specifications (P option)

Attribute

Value

Physical outputs

2

Purpose

For either alarm output or digital output

Type

Relay, SPDT type AC 1-5 A @ 250V AC; AC 15-1.5 A @ 250V AC DC 12-5A @ 24V DC; DC 13-1.5A @ 24V DC

Configuration

By means of the front keypad

Function

The outputs can work as alarm outputs but also as digital outputs, communication controlled outputs, or in any other
combination

Alarms

Up alarm and down alarm linked to the virtual alarms, other details see Virtual alarms

Response time, min

200 ms, filters excluded. Set-point on-time delay: ‘0 s’

Pulse

Signal retransmission

Total: +kWh, -kWh, +kVARh, -kVARh. Partial: +kWh, -kWh, +kVARh, -kVARh

Pulse type

The above listed variables can be connected to any output

Pulse duration

Programmable from 0.001…10.00 kWh/kVARh per pulse.

100 ms <120 ms (ON), 120 ms (OFF),

according to EN62052-31

Communication controlled outputs

The activation of the outputs is managed through the serial communication port

Insulation See

Table 42

Isolation Between Inputs and Outputs (1 minute)