Alarm and output status – Rockwell Automation 1420 PowerMonitor 500 User Manual
Page 61

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013
61
PowerMonitor 500 Unit Data Tables
Appendix A
Alarm and Output Status
Table 31 - Table Properties
CIP Assembly Instance
108
No. of Elements
2
Length in Words
2
Data Type
INT
Data Access
Read Only
Table 32 - Alarm and Output Status: Read Only Mode Data Table
Element
Modbus
Address
Length
(words)
Description / Units
Data Format
Notes
0
316385
1
Virtual alarm
UINT
Bit value: 0 = OFF
Bit value: 1 = ON
Bit position:
0: Virtual alarm 1
1: Virtual alarm 2
2: Virtual alarm 3
3: Virtual alarm 4
1
316386
1
Output (port)
UINT
Bit value
0 = OFF Bit value
1 = ON (Important: only if the port is not linked to the counter)
Bit position (LSB concept): 0: Port1
1: Port2
2 (see
Important)
316387
1
HW modules configuration
UINT
Bit value:
0 = module not present
1 = module present
Bit position
0: Relay output
1: Reserved
2: RS-485/RS-232 port
3: Ethernet Modbus
4: Reserved
5: Analog output
6: Reserved
7: Reserved
8: EtherNet/IP
9…15: Reserved
IMPORTANT
A Get_Attribute_Single command returns only elements 0 and 1 of this table.
The information in element 2 is accessible in the Identity Object, Class 0x01.