Configuration flow chart – Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 26

Advertising
background image

26

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

Chapter 3

Unit Configuration

Configuration Flow Chart

• 10 CHANGE PAS: this function lets you modify the

PASS value with a new value (from 0…9999).

• 20 BACKLIGHT: adjusts backlight time from

0…255 minutes (0 = always on).

• 50 SYSTEM: this function lets you select the type of

electrical system.
Refer to pages

17

…

18

for descriptions and wiring

diagrams corresponding to the system type

designations, such as, 3P and 3P.n.

• 60 CT RATIO: this function lets you select the value

of the CT ratio (primary/secondary ratio of the

current transformer being used). Example: if the CT

primary (current transformer) has a current of 300 A

and the secondary a current of 5 A, the CT ratio

corresponds to 60 (300 divided by 5).

• 70 PT RATIO: this function lets you select the value

of the PT (VT) ratio (primary/secondary ratio of the

potential/voltage transformer being used). Example:

if the primary of the connected PT is 20 kV and the

secondary is 100V, then the PT ratio corresponds to

200 (20,000 divided by 100).