Groundthe module – Rockwell Automation 1771-CFM Config. Flowmeter Installation Instructions User Manual

Page 11

Advertising
background image

Configurable Flowmeter Module

11

Publication 1771ĆIN043B-EN-P - July 2002

When using shielded cable wire, ground the foil shield and
drain wire only at one end ofthe cable. We recommend that

you wrap the foil shield and drain wire together and connect

them to a chassis mounting bolt. At the opposite end ofthe

cable, tape exposed shield and drain wire with electrical tape

to insulate it from electrical contact.

For additional grounding information,
see the Industrial Automation Wiring and
Grounding Guidelines
,
publication 1770-4.1.

Groundthe Module

Use the following diagrams to ground your
I/O chassis and CFM module.

foil shield

20

1

2

3

4

Remove a length ofcable

jacket from the Belden 8761 cable.

Pull the foil shield and bare

drain wire from the insulated wires.

bare drain wire

insulated wires

Twist the foil shield and drain

wire together to form a single strand.

Attach a ground lug.

20104

externalĆtooth

washers

#10 threadĆforming screw

19923

shield and drain

twisted together

SingleĆpoint Grounding

Extend shield to termination point.

Expose just enough cable to adequately

terminate inner conductors.

Use heat shrink tubing

or other suitable

insulation where wire

exits cable jacket.

19480

grounding stud

À

Use the cup washer ifcrimpĆon lugs are not used.

Chassis Ground
When you connect grounding conductors to the I/O chassis

grounding stud, place a star washer under the first lug, then

place a nut with captive lock washer on top ofeach ground lug.

Torque the nut with captive washer to 18(+3) pound-inches.

ground lug

ground lug

À

star

washer

I/O chassis

side plate

nut and captive

washer

shield and drain

twisted together

nut