Diagnostics and troubleshooting status indicators, The cfm module provides these status indicators – Rockwell Automation 1771-CFM Config. Flowmeter Installation Instructions User Manual

Page 16

Advertising
background image

Configurable Flowmeter Module

16

Publication 1771ĆIN043B-EN-P - July 2002

The CFM module returns diagnostics to the PLC processor in words
one and two of the BTR file. These diagnostics give you the word in
the BTW configuration block that has caused an error to occur.

IMPORTANT

In the event that there are multiple incorrect
BTW words, the CFM module only returns the

first incorrect word.

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

PowerĆup Bit indicates ifa valid BTW

has occurred since powerĆup or since last

switched from Program to Run mode.

Header (CFM module ID)

must be 0010.

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Error Words & Diagnostics displays

invalid BTW word number (0Ć60 BCD).

99 = invalid BTW length

Output Status reflects current

operating state ofoutputs.

b12 = Output 0 b13 = Output 1

b14 = Output 2 b15 = Output 3

VALUES:

0 = OFF

1 = ON

ЙЙЙЙЙ

ЙЙЙЙЙ

word 2

word 1

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

0

0

1

0

VALUES: 1= no or invalid BTW

0 = yes

The CFM module provides these status indicators:

Indicators

If indicator

Is ON

Is OFF

ACTIVE

the CFM module is successfully receiving

power and operational

a. Check FAULT LED Ċ ifon, follow the steps

listed under ifFAULT is ON.

b. Check the power supply.

INPUTS

(F0ĆF3 & G0ĆG3)

a signal is present at the designated

input terminal

a signal is not present at the designated

input terminal

ACTIVE

OUTPUTS

(O0ĆO3)

the module has commanded an output on

the output is off

S0 S1 S2 S3

S4 S5 S6 S7

INPUTS/OUTPUTS

FAULT

STATUS

F0 F1 F2 F3

G0 G1 G2 G3

O0 O1 O2 O3

S1

STATUS

S2
S3

PowerĆup Bit (BTR word 1, bit 00) is ON

(=1) Ċ BTW hasn't occurred since

powerĆup, or invalid BTW, or

PLC processor in Program mode

BTW is occurring
BTR is occurring

PowerĆup Bit (BTR word 1, bit 00) is OFF (=0) Ċ

valid BTW has occurred since powerĆup or since

last switched from Program to Run mode

BTW is not occurring
BTR is not occurring

FAULT

1. Turn off power to the I/O chassis

backplane and wiring arm.

2. Reseat the CFM module in the I/O

chassis.

3. Restore power to the I/O chassis

backplane and wiring arm.

Important

Ifthe fault LED remains on,

there may be an internal

problem. Contact your local

AllenĆBradley representative

for additional assistance.

normal operation

Diagnostics and

Troubleshooting

Status Indicators

Advertising