Configurable Flowmeter Module

5

Publication 1771ĆIN043B-EN-P - July 2002

Set the Input Channel

Jumpers

These jumpers

Are usedto set

flowmeter jumpers flowmeter for lowĆpass filter (70Hz)

(F0ĆF3)

or highĆspeed operation

gate jumpers

gates for +5Ć12V

(G0ĆG3)

or +12Ć30V operation

The CFM module is configured for
high-speed operation. If any input channel
will be accepting input from a mechanical
switch, you need to set the flowmeter jumper
for that input channel to filter operation.
The filter provides debouncing for the
mechanical switch.

The frequency of counting must
be less than 70Hz when the
filter mode is selected. If the
frequency exceeds 70Hz, the
CFM module will not read the
incoming pulse.

!

ATTENTION

Reposition the cover and secure with the four screws removed in step 1.

19813

Reposition the flowmeter and gate jumpers associated with each

input channel according to your requirements

FILTER

1

HIGH SPEED

5-12V

12-30V

G2

G3

G0

G1

19806

F1

F0

F3

F2

flowmeter jumpers

gate jumpers

Remove the four screws securing the side cover to the module

and remove the covers.

19805

1

In the filter position, the module will not read frequencies above 70Hz.

2

Jumpers are shown in default settings.

The flowmeter and gate jumpers

2

can be set independent ofeach other

(you can select the filter action for each flowmeter input and a voltage

for each and gate input independently).

1

2

3