Configurable Flowmeter Module

7

Publication 1771ĆIN043B-EN-P - July 2002

Install the Module

When you insert or remove the
module while backplane power is
on, or you connect or disconnect
the wiring arm with field power
applied, an electrical arc can
occur. This could cause an
explosion in hazardous location
installations. Be sure power is
removed or the area is
nonhazardous before proceeding.

Remove power from the 1771 I/O
chassis backplane before you
install the CFM module. Failure
to remove power from the
backplane could cause:

injury

equipment damage due to
unexpected operation

degradation of performance

At power-up, the active and fault indicators
are on. An initial module self-check occurs.
If there is no fault, the fault indicator
turns off. See page 16 for information on
interpreting the status indicators.

The 1771–CFM module is a modular
component of the 1771 I/O system requiring a
properly installed system chassis. Refer to
publication 1771–IN075 for detailed
information on acceptable chassis, proper
installation and grounding requirements. Limit
the maximum adjacent slot power dissipation
to 11W maximum.

!

ATTENTION

!

WARNING

Place the module in the card guides on the top and bottom ofthe

chassis that guide the CFM module into position.

Important: Apply firm even pressure on the module to seat it into its

backplane connector.

1

1771ĆA1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B I/O chassis

Snap the chassis latch over the

top ofthe module to secure it.

Swing the chassis locking bar

down into place to secure the

modules. Make sure the locking

pins engage.

1771ĆA1B, ĆA2B, ĆA3B1, ĆA4B Series B I/O chassis

19809

Attach the wiring arm (1771ĆWN) to the horizontal bar at the

bottom ofthe I/O chassis.

The wiring arm pivots upward and connects with the module so you

can install or remove the module without disconnecting the wires.

2

17643

1771ĆWN