Configurable Flowmeter Module

14

Publication 1771ĆIN043B-EN-P - July 2002

BTW WordAssignments

Word(s)

À

Bit

Á

Word(s)

À

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Block ID & Resets

1

Header

Prover Run Initialize

Overflow Reset

Total Reset

Output 1 andOutput 0 Trigger & Select

2

Output 1 Trigger

Tie Output 1 to Channel

Output 0 Trigger

Tie Output 0 to Channel

Output 3 andOutput 2 Trigger & Select

3

Output 3 Trigger

Tie Output 3 to Channel

Output 2 Trigger

Tie Output 2 to Channel

Input Channel Operating Mode

4

Channel 3

Channel 2

Channel 1

Channel 0

Input Channel Configuration

Channel 0 (words 5Ć14)

Channel 1 (words 15Ć24)

Channel 2 (words 25Ć34)

Channel 3 (words 35Ć44)

5, 15, 25, 35

Frequency

in 10ths

Bandwidth

Limit

Sampling

Termination

4 x

High Hz

Prover

Type

ЙЙЙЙ

Й

ЙЙ

Й

ЙЙЙЙ

Debounce

Filtering

Acceleration Calculation Time

6, 16, 26, 36

Minimum Frequency Sampling Time

7, 17, 27, 37

Number ofPulses to Terminate Sampling

8, 18, 28, 38

Highest Allowable Frequency

9, 19, 29, 39

Acceleration Alarm Value (what rate to trigger on)

10, 20, 30, 40

Frequency Scaler Multiplier

Â

Frequency Scaler Divisor

Â

11, 21, 31, 41

Total Scaler Multiplier

Â

12, 22, 32, 42

Total Scaler Divisor

Â

13, 23, 33, 43

Rollover Value Ċ Most Significant Digit (0Ć999 x 10,000)

14, 24, 34, 44

Rollover Value Ċ Least Significant Digit (0Ć9,999)

Output Configuration

Output 0 (words 45Ć48)

Output 1 (words 49Ć52)

Output 2 (words 53Ć56)

Output 3 (words 57Ć60)

45, 49, 53, 57

Output ON value Ċ Most Significant Digit (0Ć999 x 10,000)

46, 50, 54, 58

Output ON value Ċ Least Significant Digit (0Ć9,999)

47, 51, 55, 59

Output OFF value Ċ Most Significant Digit (0Ć999 x 10,000)

48, 52, 56, 60

Output OFF value Ċ Least Significant Digit (0Ć9,999)

À Valid BTW lengths are: 0, 1, 2, 3, 4, 14, 24, 34, 44, 48, 52, 56, 60.

Á ALL numeric values are in binary.

 When scaling is used, all outputs are still controlled by the actual value not the scaled value.

For detailed BTW descriptions,

see chapter 4, (publication

1771Ć6.5.99).