Configurable Flowmeter Module

15

Publication 1771ĆIN043B-EN-P - July 2002

Your PLC processor gets data from the CFM module using BTR
instructions in your ladder logic program. The CFM module
transfers up to 41 words to the PLC processor’s data table file.
The words contain module status and input data from each channel.

You should program a block transfer read length of zero (0). When a
BTR of 0 is programmed, the CFM module will determine the
correct number of words (41) to return.

BTR WordAssignments

Word(s)

Bit

Word(s)

15 14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Block ID & Resets

1

ЙЙЙЙЙЙ

Й

ЙЙЙЙ

Й

ЙЙЙЙЙЙ

Header

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

Й

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

Й

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

PowerĆup

bit

Output Status & Diagnostics

2

Output Status

ЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙ

Error Words & Diagnostics

Mode Indication

3

Channel 3

Channel 2

Channel 1

Channel 0

Channel 1 Status

Channel 0 Status

4

ЙЙЙ

Й

Й

Й

ЙЙЙ

Prover Status

Overrange

Alarm

Overflow

Status

Overspeed

Alarm

Acceleration

Alarm

ЙЙ

ЙЙ

ЙЙ

Prover Status

Overrange

Alarm

Overflow

Status

Overspeed

Alarm

Acceleration

Alarm

Channel 3 Status

Channel 2 Status

5

ЙЙЙ

ЙЙЙ

Prover Status

Overrange

Alarm

Overflow

Status

Overspeed

Alarm

Acceleration

Alarm

ЙЙ

ЙЙ

Prover Status

Overrange

Alarm

Overflow

Status

Overspeed

Alarm

Acceleration

Alarm

Input Channel Data

Channel 0 (words 6Ć14)

Channel 1 (words 15Ć23)

Channel 2 (words 24Ć32)

Channel 3 (words 33Ć41)

6, 15, 24, 33

Percent ofFull Scale (Rate % ofHigh RPM value)

7, 16, 25, 34

Frequency (0Ć120 ) MSD

8, 17, 26, 35

Frequency (0Ć999) LSD

9, 18, 27, 36

Total MSD (0Ć999)

10, 19, 28, 37

Total LSD (0Ć9,999)

11, 20, 29, 38

Acceleration (rate ofchange offrequency)

12, 21, 30, 39

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

Direction

13, 22, 31, 40

Prover Total Count Value or Store Count Value Ċ MSD (0Ć999)

14, 23, 32, 41

Prover Total Count Value or Store Count Value Ċ LSD (0Ć9,999)

not used

ЙЙЙ

ЙЙЙ

* Numeric values are in binary except for Diagnostics (word 2, bits 00Ć07)*

For detailed BTR descriptions,

see chapter 5, (publication

1771Ć6.5.99).

Interpret Module Status