Specifications, Specifications 21 – Rockwell Automation 1756-EN3TR ControlLogix EtherNet/IP Communication Module Installation Instructions User Manual

Page 21

Advertising
background image

21

Publication

1756-IN612B-EN-P - December 2009

Specifications

Technical Specifications - 1756-EN2TR and 1756-EN3TR

Attribute

Value

Module location

Any slot in the ControlLogix chassis

Backplane current (mA)
at 5.1V DC

1 A

Backplane current (mA)
at 24V DC

3 mA

Isolation voltage

30 V (continuous), Basic Insulation Type, Ethernet to system
No isolation between USB and system
Type tested at 853V AC for 60 s

Power consumption,
max

5.1 W

Power dissipation

5.1 W

Wire size

Ethernet connections:

RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e
minimum cable according to TIA 568-B.1 or Category 5 cable
according to ISO/IEC 24702.

Wiring category

1 - on communication ports

(1)

(1)

Use this Conductor Category information for planning conductor routing.

Refer to Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

North American temp
code

T4A

Recommended USB
cable for USB port

For hazardous environments, Samtec cable, PN RSP-119350

USB port

USB 1.1

USB device,

USB series B receptacle

Enclosure type rating

None (open-style)

Advertising