Specifications – Rockwell Automation 1792-IB8XOB8PLP INSTL INSTR ARMORBLOCK LP 8/8 User Manual
Page 10

ArmorBlock-LP 8 Input/8 Output Module
10
Publication 1792-5.8 – December 1997
Sensor Short Circuit Indicator OVL
Indication
Status
OFF
Sensor source voltage operating correctly
Solid Red
1 or more Sensor source voltage shorts, output
overload or no load condition
Output I/O Status Indicators A and B
Indication
Status
OFF
Output is off
Yellow
Output is on
Input I/O Status Indicators A and B
Indication
Status
OFF
No valid input signal present
Yellow
Valid input signal present
Module and Sensor Power Supply Status Indicators U
S
and U
L
Indication
Status
OFF
Power supply is not functioning correctly
Green
Power Supply is operating
Specifications
8 Input/8 Output Module – Cat. No. 1792-IB8XOB8PLP
Input Specifications
Inputs per Block
8 sinking inputs labeled 1, 3, 5, and 7
On-state Voltage Range
12–30V dc
On-state Current
Maximum
Minimum
15.0mA @ 30V dc
1.6mA @ 12V dc
Off-state Voltage
Maximum
5V dc
Off-state Current
Minimum
0.8mA
Transition Voltage
5–12.0V dc
Transition Current
0.8–2.2mA
Input Signal Delay
Off to On or On to Off
1ms maximum
Specifications continued on next page.