Rockwell Automation 1792-IB8XOB8PLP INSTL INSTR ARMORBLOCK LP 8/8 User Manual
Page 7

ArmorBlock-LP 8 Input/8 Output Module
7
Publication 1792-5.8 – December 1997
Type of I/O Connections
Consumes
Produces
Polled
1 Bytes
2 Bytes
Bit Strobe
0 Bytes
2 Bytes
Change of State
0 Bytes
2 Bytes
Polled device – a master initiates communication by sending its polled
I/O message to the ArmorBlock module. The 8 input/8 output module
consumes the message, updates outputs, and produces a response that
reflects the status of 1) its inputs, and 2) any input or output faults.
Change of state device – productions occur when an input or fault
condition changes. If neither has occurred within the “expected packet
rate,” a heartbeat production occurs. This heartbeat production tells the
scanner module that the ArmorBlock module is alive and ready to
communicate.
Bit Strobe device – a master initiates communication by sending its bit
strobe I/O message. All bit strobed devices then respond. The 8 input/8
output module consumes the message, and produces a response that
reflects the status of inputs and outputs.
Refer to the table below for the word/bit definitions.
Bit
07
06
05
04
03
02
01
00
Produces
I7B
I5B
I3B
I1B
I7A
I5A
I3A
I1A
Produces
IS
OF
Reserved
Consumes
O8B
O6B
O4B
O2B
O8A
O6A
O4A
O2A
Where: I = Input
O = Output
IS = Sensor source voltage fault
OF = Output fault status