ArmorBlock-LP 8 Input/8 Output Module

7

Publication 1792-5.8 – December 1997

Type of I/O Connections

Consumes

Produces

Polled

1 Bytes

2 Bytes

Bit Strobe

0 Bytes

2 Bytes

Change of State

0 Bytes

2 Bytes

Polled device – a master initiates communication by sending its polled
I/O message to the ArmorBlock module. The 8 input/8 output module
consumes the message, updates outputs, and produces a response that
reflects the status of 1) its inputs, and 2) any input or output faults.

Change of state device – productions occur when an input or fault
condition changes. If neither has occurred within the “expected packet
rate,” a heartbeat production occurs. This heartbeat production tells the
scanner module that the ArmorBlock module is alive and ready to
communicate.

Bit Strobe device – a master initiates communication by sending its bit
strobe I/O message. All bit strobed devices then respond. The 8 input/8
output module consumes the message, and produces a response that
reflects the status of inputs and outputs.

Refer to the table below for the word/bit definitions.

Bit

07

06

05

04

03

02

01

00

Produces

I7B

I5B

I3B

I1B

I7A

I5A

I3A

I1A

Produces

IS

OF

Reserved

Consumes

O8B

O6B

O4B

O2B

O8A

O6A

O4A

O2A

Where: I = Input

O = Output
IS = Sensor source voltage fault
OF = Output fault status