ArmorBlock-LP 8 Input/8 Output Module

9

Publication 1792-5.8 – December 1997

30197–M

NS = Network Status Indicator

OVL = Sensor and Output

Status Indicator

U

S

= Output Power

Supply Status Indicator

U

L

= Module Power Supply

Status Indicator

A and B = Input

and Output I/O

Status Indicators

MS = Module Status

Indicator

Output

Connector

OUT

IN

1

2

34

5

6

7

8

A

B

A

B

A

B

A

B

A

B

A

B

A

B

A

B

Note: This module contains a circuit to protect the DeviceNet power supply from short

circuits in an attached sensor or sensor cable. If you connect a sensor while the
module is powered, the surge current produced by the sensor can cause the
module to fault. This operation is normal.

Network Status Indicator NS

Indication

Status

Flashing Green

On-line, not connected

Solid Green

Link OK, on-line connected

Flashing Red

At least 1 I/O connection is in the timed-out state

Solid Red

Incorrect baud rate, or a duplicate Mac ID exists

Module Status Indicator MS

Indication

Status

OFF

No power, or no network access

Flashing
Green/OFF

On-line but not connected

Solid Green

On-line, link okay, connected

Flashing Red

Recoverable fault

Solid Red

Critical failure