ArmorBlock-LP 8 Input/8 Output Module
9
Publication 1792-5.8 – December 1997
30197–M
NS = Network Status Indicator
OVL = Sensor and Output
Status Indicator
U
S
= Output Power
Supply Status Indicator
U
L
= Module Power Supply
Status Indicator
A and B = Input
and Output I/O
Status Indicators
MS = Module Status
Indicator
Output
Connector
OUT
IN
1
2
34
5
6
7
8
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
Note: This module contains a circuit to protect the DeviceNet power supply from short
circuits in an attached sensor or sensor cable. If you connect a sensor while the
module is powered, the surge current produced by the sensor can cause the
module to fault. This operation is normal.
Network Status Indicator NS
Indication
Status
Flashing Green
On-line, not connected
Solid Green
Link OK, on-line connected
Flashing Red
At least 1 I/O connection is in the timed-out state
Solid Red
Incorrect baud rate, or a duplicate Mac ID exists
Module Status Indicator MS
Indication
Status
OFF
No power, or no network access
Flashing
Green/OFF
On-line but not connected
Solid Green
On-line, link okay, connected
Flashing Red
Recoverable fault
Solid Red
Critical failure