6

Publication 1792-5.8 – December 1997

Connecting the Output Power Wiring

Connect output power wiring to the 3-pin mini-connector on the end of
the block.

Important: The outputs use electronic overcurrent fault protection. Make certain
your output power supply can handle overcurrent events.

1

2

3

Output Power Mini-Connector

Pin 1 = Chassis ground

Pin 2 = +24V dc

Pin 3 = Negative/Return

(View into pins)

Connecting the DeviceNet Wiring

Connect DeviceNet wiring to the 5-pin mini-connector on the end of the
block. Connections are shown below.

1

2

3

DeviceNet Mini-Connector

Pin 1 = Drain (Bare)

Pin 2 = V+ (Red)

Pin 3 = V– (Black)

(View into pins)

4

5

Pin 4 = CAN–HI (White)

Pin 5 CAN–LO (Blue)

Note: Colors are
DeviceNet standard

Communicate with Your ArmorBlock Module

This ArmorBlock module’s I/O is exchanged with the master through a
poll, bit strobe or change of state connection.

When set for Polled, Bit Strobe, or change of state, the module consumes
and produces as follows:

Advertising