ArmorBlock-LP 8 Input/8 Output Module

3

Publication 1792-5.8 – December 1997

Set the Node Address

Each ArmorBlock-LP comes with its internal program set for node
address 63 and a communication rate of 125K bps. To set the node
address and communication rate, you need the following:

host computer with DeviceNet Manager Software (or similar
configuration software tool)

1770-KFD RS-232 module (or similar interface)

suitable cables to connect the 1770-KFD to your module and to
connect the 1770-KFD to your host computer

Set up a system (as shown below) to communicate with your
ArmorBlock module to set the node address and communication rate to
meet your system requirements.

30195–M

Host computer with

DeviceNetManager

software

Power from 9V dc power supply adapter

1770-KFD

RS-232 module

Power Supply

Open style connector

to sealed mini–connector

Mount the ArmorBlock Module

Mount the block module directly to the machine or device. Complete
mounting dimensions are shown below.