ArmorBlock-LP 8 Input/8 Output Module

11

Publication 1792-5.8 – December 1997

Sensor Source

Voltage

Current

Minimum 13V dc @ 400mA out and
DeviceNet power = 15V dc
50mA per point, 0.4A total per module

Output Specifications

Output Power Supply

Note: In order to comply with CE Low Voltage Directives,
you must use a Safety Extra Low Voltage (SELV) or a
Protected Extra Low Voltage (PELV) power supply to
power the outputs of this module.

Outputs per Block

8 Sourcing Outputs – labeled 2, 4, 6 and 8

Output Voltage Range

19–30V dc

On-state Current Maximum

1.0A per output

On-state Voltage Maximum

3V dc at rated current

Module Current (all outputs on)

8.0A per module

Off-state Leakage Current

1.5mA maximum per output

Specifications continued on next page.

General Specifications

Indicators

Network Status – red/green
Module Status – red/green
Sensor Supply Status – green
Module Power Supply Status – green
Short Circuit Sensor – red
I/O Status – yellow

Communication Rate in Baud

125k, 250k, 500k software selectable

DeviceNet Power Voltage

Current

11.0 – 25.0V dc
100mA (no powered sensors); 500mA (full sensor load)

Specifications continued on next page.