Troubleshoot with the indicators – Rockwell Automation 1792-IB8XOB8PLP INSTL INSTR ARMORBLOCK LP 8/8 User Manual

Page 8

Advertising
background image

ArmorBlock-LP 8 Input/8 Output Module

8

Publication 1792-5.8 – December 1997

Word

Bit

Description

Produces

00–07 Input Status bits – when the bit is set (1), the input is on. Bit 00

corresponds to input 1A, bit 01 corresponds to input 3A, bit 02 to
input 5A, bit 03 input 7A. Bit 04 corresponds to input 1B, bit 05 to
input 3B, bit 06 to input 5B, and bit 07 to input 7B.

Produces

00–05 Reserved

Produces

06

OF = output fault status bit – indicates presence of field power
(default). Can also indicate no load or overload condition when
diagnostics are enabled. Refer to publication 1792-2.1, ArmorBlock
and AmorBlock-LP Product Data.

07

IS = Sensor source voltage fault bit – this bit is set (1) when the
sensor source voltage is faulted.

Consumes

00–07 Output bits – when the bit is set (1), the output is on. Bit 00

corresponds to output 2A, bit 01 corresponds to output 4A, bit 02 to
output 6A, bit 03 output 8A. Bit 04 corresponds to output 2B, bit 05
to output 4B, bit 06 to output 6B, and bit 07 to output 8B.

Troubleshoot with the Indicators

The ArmorBlock I/O module has the following indicators:

Network status indicators (NS)

Module status indicator (MS)

Individual I/O status indicators A and B

Power Status indicators

module power

output voltage

sensor and output status

Advertising