5-6 Once You Have Completed the Installation

Publication 1784-IN004E-EN-P - April 2005

7. Enter a name for the new RSLinx driver and click OK.

The new driver will be added to the list of configured RSLinx drivers. (Your screen
will display the drivers you have configured on your system.)

TIP

Browse the network by expanding the DeviceNet port on the desired
1784-PCIDS communication card.

The driver’s Status should be
“Running”. If not, there is a
problem. Check the physical
connection to the 1784-PCIDS
card. If the physical connection is
intact, verify the network baud
rate and ensure that the
1784-PCIDS card’s node number is
unique. Also check the external
24V power connections. The
Network LED on the 1784-PCIDS
card should be solid or flashing
green when the card is connected to
the DeviceNet network.