Interpret Status Indicators (LEDs) 7-5

Publication 1784-IN004E-EN-P - April 2005

Network (NET) Status Indicator

This bi-color (green/red) LED indicates the status of the communication link.

condition

status

indicates

off

not powered,

not online

Device is not online.

The device has not completed the Dup_MAC_ID test yet.

The device may not be powered; look at the Module Status
LED.

flashing green

1

online,

not connected

Device is online, but has no connections in the established
state.

The device has passed the Dup_MAC_ID test, is online, but
has no established connections to other nodes.

green

link okay, online,
connected

The device is online and has connections in the established
state.

flashing red

1

connection time-out

One or more I/O connections are in the timed-out state.

red

critical link failure

Failed communication device. The device has detected an
error that has rendered it incapable of communicating on
the network (Duplicate MAC ID or Bus-off).

Check network integrity and baud rate of all devices. Then
cycle power to the card by shutting down and cycling power
to your computer.

1

The flash rate of the LED is approximately 1 flash per second. The LED should be on for approximately

0.5 seconds and off for approximately 0.5 seconds.