12 Compact 1769-OF8V Analog Output Module

Publication 1769-IN066D-EN-P - June 2010

Wire Size and Terminal Screw Torque

Each terminal accepts up to two wires with the following restrictions:

I/O Memory Mapping

Output Data File

For each module, slot x, words 0-7 in the output data file contain the channel 0 through
channel 7 output data. Word 8 is used to unlatch any alarm condition that has been latched.
Refer to the Compact™ Analog I/O User Manual, publication number 1769-UM002 for
additional details.

• SGN = Sign bit in two’s complement format.
• UU = Unlatch under-range (or low-clamp exceeded) alarm.
• UO = Unlatch over-range (or high-clamp exceeded) alarm.

Wire Type

Wire Size

Terminal Screw

Torque

Retaining Screw

Torque

Solid

Cu-90°C (194°F)

#14 to #22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

Stranded

Cu-90°C (194°F)

#16 to #22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

IMPORTANT

If you are using RSLogix 5000, version 15, please refer to RSLogix 5000,
Version 15, Controller Tags on page 17.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

SGN

Analog Output Data Channel 0

1

SGN

Analog Output Data Channel 1

2

SGN

Analog Output Data Channel 2

3

SGN

Analog Output Data Channel 3

4

SGN

Analog Output Data Channel 4

5

SGN

Analog Output Data Channel 5

6

SGN

Analog Output Data Channel 6

7

SGN

Analog Output Data Channel 7

8

UU7

UO7 UU6 UO6 UU5 UO5 UU4 UO4 UU3 UO3 UU2 UO2 UU1 UO1 UU0 UO0