Hazardous location considerations – Rockwell Automation 1769-OF8V Compact Analog Output Module User Manual

Page 26

Advertising
background image

26 Compact 1769-OF8V Analog Output Module

Publication 1769-IN066D-EN-P - June 2010

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous
locations only. The following WARNING statement applies to use in hazardous locations.

Specification

1769-OF8V

System Power Supply Distance
Rating

The module may not be more than 8 modules away from the system power
supply.

Optional 24V dc Class 2 Power

Supply Voltage Range

(1)

20.4 V to 26.4 V dc

Recommended Cable

Belden™ 8761 (shielded)

Vendor I.D. Code

1

Product Type Code

10

Product Code

39

Input Words

11

Output Words

9

Configuration Words

64

(1)

Failure to use a Class 2 power supply without regulation within these limits could result in improper module operation.

WARNING

EXPLOSION HAZARD

• Substitution of components may impair suitability for Class I,

Division 2.

• When in hazardous locations, turn off power before replacing or

wiring modules.

• Do not disconnect components unless power has been switched off

or the area is known to be non-hazardous.

• This product must be installed in an enclosure.

All wiring must comply with N.E.C. article 501-4(b).

Advertising