General Specifications

Specification

Value

Dimensions

118 mm (height) x 87 mm (depth) x 35 mm (width)
height including mounting tabs is 138 mm

4.65 in. (height) x 3.43 in (depth) x 1.38 in (width)
height including mounting tabs is 5.43 in.

Approximate Shipping Weight
(with carton)

263g (0.58 lbs.)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +60°C (32°F to +140°F)

Operating Humidity

5% to 95% non-condensing

Operating Altitude

2000 meters (6561 feet)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Relay Operation: 2G

Shock

Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)

Non-Operating: 40G panel mounted
(30G DIN rail mounted)

Agency Certification

• C-UL certified (under CSA C22.2 No. 142)
• UL 508 listed
• CE compliant for all applicable directives

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D
(ISA 12.12-01, C-UL under CSA C22.2 No. 213)

Radiated and Conducted Emissions

EN 61000-6-4 and CISPR 11 Group 1, Class A

Electrical /EMC:

The module has passed testing at the following levels:

• ESD Immunity (IEC 61000-4-2)

• 4 kV contact, 8 kV air, 4 kV indirect

• Radiated Immunity

(IEC 61000-4-3)

• 10 V/m, 80 to 1000 MHz, 80% amplitude modulation,

+900 MHz keyed carrier

• Fast Transient Burst

(IEC 61000-4-4)

• 2 kV, 5 kHz

• Surge Immunity (IEC 61000-4-5)

• 1 kV galvanic gun

• Conducted Immunity

(IEC 61000-4-6)

• 10V rms, 0.15 to 80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.