Configuration data file – Rockwell Automation 1769-OF8V Compact Analog Output Module User Manual

Page 14

Advertising
background image

14 Compact 1769-OF8V Analog Output Module

Publication 1769-IN066D-EN-P - June 2010

Configuration Data File

The manipulation of the bits from this file is normally done with programming software (e.g.
RSLogix 500, RSNetWorx for DeviceNet, etc.) during initial configuration of the system. In
that case, graphical screens are provided by the programmer to simplify configuration.
However, some systems, like the 1769-ADN DeviceNet Adapter, also allow the bits to be
altered as part of the control program, using communication rungs. In that case, it is
necessary to understand the bit arrangement. The channel configuration words, the first two
words of each eight word group, are described on page 16. Refer to the Compact™ Analog I/O

User Manual, publication number 1769-UM002 for additional details.

Word

Description

Word

Description

0

Channel 0 Configuration Word 0

24

Channel 3 Configuration Word 0

1

Channel 0 Configuration Word 1

25

Channel 3 Configuration Word 1

2

Channel 0 Fault Value Word

26

Channel 3 Fault Value Word

3

Channel 0 Program Idle Mode Word

27

Channel 3 Program Idle Mode Word

4

Channel 0 Low Clamp

28

Channel 3 Low Clamp

5

Channel 0 High Clamp

29

Channel 3 High Clamp

6

Channel 0 Ramp Rate

30

Channel 3 Ramp Rate

7

Channel 0 Spare

31

Channel 3 Spare

8

Channel 1 Configuration Word 0

32

Channel 4 Configuration Word 0

9

Channel 1 Configuration Word 1

33

Channel 4 Configuration Word 1

10

Channel 1 Fault Value Word

34

Channel 4 Fault Value Word

11

Channel 1 Program Idle Mode Word

35

Channel 4 Program Idle Mode Word

12

Channel 1 Low Clamp

36

Channel 4 Low Clamp

13

Channel 1 High Clamp

37

Channel 4 High Clamp

14

Channel 1 Ramp Rate

38

Channel 4 Ramp Rate

15

Channel 1 Spare

39

Channel 4 Spare

16

Channel 2 Configuration Word 0

40

Channel 5 Configuration Word 0

17

Channel 2 Configuration Word 1

41

Channel 5 Configuration Word 1

18

Channel 2 Fault Value Word

42

Channel 5 Fault Value Word

19

Channel 2 Program Idle Mode Word

43

Channel 5 Program Idle Mode Word

20

Channel 2 Low Clamp

44

Channel 5 Low Clamp

21

Channel 2 High Clamp

45

Channel 5 High Clamp

22

Channel 2 Ramp Rate

46

Channel 5 Ramp Rate

23

Channel 2 Spare

47

Channel 5 Spare

Advertising