Compact 1769-OF8V Analog Output Module 13

Publication 1769-IN066D-EN-P - June 2010

Input Data File

For each module, slot x, input data file words 3-10 contain the state of the module’s output
data (output data echo) file words 0-7. During normal operation, these input words represent

the analog values that the outputs are directed to by the control program.

• PF = Analog power fail.
• S = General status (over-range, under-range, or open-circuit).
• D = Open-circuit diagnostics.
• H = Output held bit.
• U = Under-range (or low-clamp exceeded) alarm.
• O = Over-range (or high-clamp exceeded) alarm.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

PF

S7

S6

S5

S4

S3

S2

S1

S0

1

D3

H3

U3

O3

D2

H2

U2

O2

D1

H1

U1

O1

D0

H0

U0

O0

2

D7

H7

U7

O7

D6

H6

U6

O6

D5

H5

U5

O5

D4

H4

U4

O4

3

Channel 0 Data Value

4

Channel 1 Data Value

5

Channel 2 Data Value

6

Channel 3 Data Value

7

Channel 4 Data Value

8

Channel 5 Data Value

9

Channel 6 Data Value

10

Channel 7 Data Value

IMPORTANT

The output module’s input data file reflects the analog output data echo of
the module, not necessarily the electrical state of the output terminals. It
does not reflect shorted or open outputs.