Output specifications – Rockwell Automation 1769-OF8V Compact Analog Output Module User Manual

Page 24

Advertising
background image

24 Compact 1769-OF8V Analog Output Module

Publication 1769-IN066D-EN-P - June 2010

Output Specifications

Specification

1769-OF8V

Analog Normal Operating Ranges

(1)

(1)

The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will
continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the
normal operating range.

± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc

Full Scale Analog Ranges

(1)

± 10.5V dc, -0.5 to 10.5V dc, -0.5 to 5.25V dc,
0.5 to 5.25V dc

Number of Outputs

8 single-ended

Bus Current Draw (max.)

145 mA at 5V dc

135 mA at 24V dc

(2)

(2)

If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA.

Heat Dissipation

2.16 Total Watts (All points - 10.5V into 1 k

Ω - worst case calculated.)

Digital Resolution Across Full Range

16 bits plus sign (bipolar)

±10V dc: 15.89 bits, 330 µV/bit
0 to +5V dc: 13.89 bits, 330 µV/bit
0 to +10V dc: 14.89 bits, 330 µV/bit
+1 to +5V dc: 13.57 bits, 330 µV/bit

Conversion Rate (all channels) max.

5.0 ms

Step Response to 63%

(3)

(3)

Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until
the device is at 63% of full range.

<2.9 ms

Current Load Output

10 mA max.

Load Range Output

> 1 k

Ω at 10V dc

Max. Capacitive Load

1 µF

Field Calibration

None required

Overall Accuracy

(4)

(4)

Includes offset, gain, drift, non-linearity and repeatability error terms.

±0.5% full scale at 25°C

Advertising