18 Compact 1769-OF8V Analog Output Module
Publication 1769-IN066D-EN-P - June 2010
Local:1:C.Ch1En
BOOL
Decimal
+
Local:1:C.Ch1Range
SINT
Decimal
+
Local:1:C.Ch1DataFormat
SINT
Decimal
+
Local:1:C.Ch1FaultValue
INT
Decimal
+
Local:1:C.Ch1ProgValue
INT
Decimal
+
Local:1:C.Ch1LClampValue
INT
Decimal
+
Local:1:C.Ch1HClampValue
INT
Decimal
+
Local:1:C.Ch1RampRate
INT
Decimal
Tag Name
To Select
Make These Bit Settings
(1)
15-8
7
6
5
4
3
2
1
0
Ch#ProgToFaultEn
Enable
1
Disable
0
Ch#HoldForInit
Enable
1
Disable
0
Ch#ProgMode
Enable
1
Disable
0
Ch#FaultMode
Enable
1
Disable
0
Ch#RampEn
Enable
1
Disable
0
Ch#AlarmLatchEn
Enable
1
Disable
0
Ch#OverRangeInterruptEn
Enable
1
Disable
0
Ch#UnderRangeInterruptEn
Enable
1
Disable
0
Ch#En
Enable
1
Disable
0
Ch#Range
-10…+10V dc
0
0
0…5V dc
0
1
0…10V dc
1
0
1…5V dc
1
1
Ch#DataFormat
Raw/proportional
counts
0
0
Engineering units
0
1
Scaled for PID
1
0
Percent range
1
1
(1)
All bit positions left blank in table must be set to 0.