Rockwell Automation 1769-OF8V Compact Analog Output Module User Manual

Page 15

Advertising
background image

Compact 1769-OF8V Analog Output Module 15

Publication 1769-IN066D-EN-P - June 2010

• E = Channel Enable: (0 = Disabled, 1 = output 0 and hold Enabled, process changes)
• Reserved = Set to zero
• SIU = System interrupt low clamp, under-range alarms: (0 = Disabled, 1 = Enabled)
• SIO = System interrupt high clamp, over-range alarms: (0 = Disabled, 1 = Enabled)
• LA = Latch low/high clamp, under/over-range alarms: (0 = Disabled, 1 = Enabled)
• ER = Enable ramping: (0 = Disabled, 1 = Enabled. Ramp rate limited by fault states.)
• FM = Fault mode: (0 = Hold Last State, 1 = User Defined Value)
• PM = Program mode: (0 = Hold Last State, 1 = User Defined Value)
• HI = Hold for initialization: (0 = Disabled, 1 = Enabled)
• PFE = Program/idle to fault enable: (0 = Disabled, 1 Enabled)

Word

Description

Word

Description

48

Channel 6 Configuration Word 0

56

Channel 7 Configuration Word 0

49

Channel 6 Configuration Word 1

57

Channel 7 Configuration Word 1

50

Channel 6 Fault Value Word

58

Channel 7 Fault Value Word

51

Channel 6 Program Idle Mode Word

59

Channel 7 Program Idle Mode Word

52

Channel 6 Low Clamp

60

Channel 7 Low Clamp

53

Channel 6 High Clamp

61

Channel 7 High Clamp

54

Channel 6 Ramp Rate

62

Channel 7 Ramp Rate

55

Channel 6 Spare

63

Channel 7 Spare

Word/Bit 15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Word 0

E

Reserved

SIU SIO LA

ER

FM PM HI

PFE

Word 1

Reserved

Output Data

Format Select

Reserved

Output
Type/Range

Advertising