10 FLEX I/O 8 Input HART Analog Module
Publication
1794-IN108D-EN-P - January 2014
3. Refer to the Figure for other configurations.
4. Connect +V DC power to terminal 34 on the 34 to 51 row (C).
5. Connect -V to terminal 35 on the 34 to 51 row (C).
6. If continuing power to the next terminal base unit, connect a jumper
from terminal 50 (+V) on this base unit to terminal 34 on the next
base unit.
If continuing common to the next terminal base unit, connect a
jumper from terminal 51 (-V) on this base unit to terminal 35 on the
next base unit.
ATTENTION
The 1794-IE8H module shall be used only with Listed Allen-Bradley (Rockwell
Automation) Power Supply (catalog number 1794-PS13) or Listed Class 2 source.
ATTENTION
To reduce susceptibility to noise, power analog modules and digital modules
from separate power supplies.
Wire Connections
Input
Input
Source
Input
Signal
Input
Return
Input
Input
Source
Input
Signal
Input
Return
Input 0
A-0
A-1
A-2
Input 4
B-17
B-18
B-19
Input 1
A-4
A-5
A-6
Input 5
B-21
B-22
B-23
Input 2
A-8
A-9
A-10
Input 6
B-25
B-26
B-27
Input 3
A-12
A-13
A-14
Input 7
B-29
B-30
B-31
+V
Terminals 34 and 50
-V
Terminals 35 and 51