Rockwell Automation 1794-IE8H, Series B FLEX I/O 8 Input Hart Analog Module Installation Instructions User Manual

Page 33

Advertising
background image

FLEX I/O 8 Input HART Analog Module 33

Publication

1794-IN108D-EN-P - January 2014

Flexbus current external

input

(2)

5V DC 80 mA

24V DC 190 mA

Power dissipation, max

3.9 W @ 31.2V DC

Enclosure type rating

None (open-style)

Terminal base screw torque

Determined by installed terminal base

Wire size

Determined by installed terminal base

Wiring category

(3)

2 - on signal ports

2 - on power ports

Wire type

Shielded on signal ports

Thermal dissipation, max

13.5 BTU/hr @31.2V DC

Keyswitch position

3

Dimensions (HxWxD),
approx.

46.0 x 94.0 x 75.0 mm (1.8 x 3.7 x 2.95 in.)

Weight, approx.

200 g (7.05 oz)

North American
temperature code

T4A

IEC Temp Code

T4

(1)

Includes offset, gain, nonlinearity. and repeatability error terms.

(2)

If 24V DC is removed from the module, input resistance = 10 k

Ω.

(3)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

FLEX I/O 8 Input HART Analog Module - 1794-IE8H, Series B

Attribute