16 FLEX I/O 8 Input HART Analog Module

Publication

1794-IN108D-EN-P - January 2014

Digital Filter

6

0 1 1 0 4…20 mA as

%

4.00

22.00

0

(0%)

10607

(106.07%)

0.17% of
4...20 mA

7

0 1 1 1 4…20 mA as

unsigned
integer

4.00

20.00

0

(4 mA)

65535

(20 mA)

0.03% of
4...20 mA

8

1 0 0 0 Not assigned

9

1 0 0 1

10

1 0 1 0

11

1 0 1 1 0...20 mA as

A/D count

0.00

22.00

0

(0 mA)

55000

(22 mA)

0.04% of
0...20 mA

12

1 1 0 0 4...20 mA as

%

3.60

21.00

-250

(-2.50%)

10625

(106.25%)

0.16% of
4...20 mA

13

1 1 0 1 4...20 mA as

%

3.00

21.00

-625

(-6.25%)

10625

(106.25%)

0.16% of
4...20 mA

14

1 1 1 0 4...20 mA as

%

2.00

22.00

-1250

(-12.50%)

11250

(112.50%)

0.16% of
4...20 mA

15

1 1 1 1 Not assigned

Digital Filter
frequency

Decimal
Value

Bits

Digital Filter
frequency

Decimal
Value

Bits

2

1

0

2

1

0

10

9

8

10

9

8

0.5 Hz

7

0

0

0

10 Hz

3

1

0

0

1 Hz

6

0

0

1

Not applicable

(1)

(1)

Decimal Values 2, 1 and 0 are not applicable. Values will Revert to the last valid configuration (in case
of original start-up this would be default configuration) and set module Diagnostic Status to "2"
configuration failure.

2

1

0

1

2 Hz

5

0

1

0

Not applicable

1

1

1

0

4 Hz

4

0

1

1

Not applicable

0

1

1

1

Data Format - Write Words 2 and 3

Data
Format

Bits

Format

Signal Range User Range

Resolution

15 14 13 12

11 10 9

8

7

6

5

4

LO

HI

LO

HI

3

2

1

0