Prevent electrostatic discharge – Rockwell Automation 1794-IE8H, Series B FLEX I/O 8 Input Hart Analog Module Installation Instructions User Manual

Page 4

Advertising
background image

4 FLEX I/O 8 Input HART Analog Module

Publication

1794-IN108D-EN-P - January 2014

Prevent Electrostatic Discharge

ATTENTION

This product is grounded through the DIN rail to chassis ground. Use zinc plated
yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN
rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are
poor conductors, can result in improper or intermittent grounding. Secure DIN
rail to mounting surface approximately every 200 mm (7.8 in.) and use
end-anchors appropriately.

ATTENTION

This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:

Touch a grounded object to discharge potential static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component boards.

Do not touch circuit components inside the equipment.

Use a static-safe workstation, if available.

Store the equipment in appropriate static-safe packaging when not in
use.

ATTENTION

To comply with the CE Low Voltage Directive (LVD), all connected I/O must be
powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

Advertising