Configuration map (series a mode) – Rockwell Automation 1794-IE8H, Series B FLEX I/O 8 Input Hart Analog Module Installation Instructions User Manual
Page 24

24 FLEX I/O 8 Input HART Analog Module
Publication
1794-IN108D-EN-P - January 2014
Configuration Map (Series A Mode)
Word
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Reserved High and Low Error
Level 0...3
u/d
0...3
Filter Cutoff
0...3
Data Format 0...3
FM
0...3
1
Sq. Root
Thresh.
High and Low Error
Level 4...7
u/d
4...7
Filter Cutoff
4...7
Data Format 4...7
FM
4...7
Where: u/d = remote transmitter error up/down
FM = fault mode
Sq. Root Thresh. = square root threshold
Fault Mode (Series A Mode)
Word 0 Bit 00
Fault enable for Channels 0...3
Word 1 Bit 00
Fault enable for Channels 4...7
Where: O = disable
1 = enable with wire-off overload
Filter Cutoff Selections (Series A Mode)
Word
Bits
Description
0
07
06
05
Channels 0...3
1
07
06
05
Channels 4...7
0
0
0
Reserved
0
0
1
Reserved
0
1
0
Reserved
0
1
1
10 Hz (100 ms)
1
0
0
4 Hz (250 ms)
1
0
1
2 Hz (500 ms)
1
1
0
1 Hz (1 s)
1
1
1
0.5 Hz (2 s)