FLEX I/O 8 Input HART Analog Module 25

Publication

1794-IN108D-EN-P - January 2014

Remote Transmitter Error Up/Down (Series A Mode)

Word 0 Bit 08

Up/down for Channels 0...3

Word 1 Bit 08

Up/down for Channels 4...7

Where: O = up

1 = down

Data Format (Series A Mode)

Word

Bits

Description

0

04

03

02

01

Channels 0...3

1

04

03

02

01

Channels 4...7

0

0

0

0

0…22 mA = 0...22,000 with error steps (default)

0

0

0

1

0…22 mA = 0…110%, with error steps

0

0

1

0

0…22 mA = 0…104.8%, square root, with error steps

0

0

1

1

0…20 mA = 0…65,535, unsigned integer, with error steps

0

1

0

0

2…22 mA, with error steps

0

1

0

1

2…22 mA = -12.5%…112.5%, with error steps

0

1

1

0

4…22 mA = 0…106%, square root, with error steps

0

1

1

1

4…20 mA = 0…65,535, unsigned integer, with error steps

1

0

0

0

Not assigned

1

0

0

1

Not assigned

1

0

1

0

Not assigned

1

0

1

1

0…22 mA = A/D count, with fixed error

1

1

0

0

3.6…21 mA = NAMUR NE 43, with fixed error

1

1

0

1

3…21 mA = -6.25 to 106.25% with fixed error

1

1

1

0

2…22 mA = -12.5 to 112.5% with fixed error

1

1

1

1

Not assigned