Rockwell Automation 1794-IE8H, Series B FLEX I/O 8 Input Hart Analog Module Installation Instructions User Manual
Page 25

FLEX I/O 8 Input HART Analog Module 25
Publication
1794-IN108D-EN-P - January 2014
Remote Transmitter Error Up/Down (Series A Mode)
Word 0 Bit 08
Up/down for Channels 0...3
Word 1 Bit 08
Up/down for Channels 4...7
Where: O = up
1 = down
Data Format (Series A Mode)
Word
Bits
Description
0
04
03
02
01
Channels 0...3
1
04
03
02
01
Channels 4...7
0
0
0
0
0…22 mA = 0...22,000 with error steps (default)
0
0
0
1
0…22 mA = 0…110%, with error steps
0
0
1
0
0…22 mA = 0…104.8%, square root, with error steps
0
0
1
1
0…20 mA = 0…65,535, unsigned integer, with error steps
0
1
0
0
2…22 mA, with error steps
0
1
0
1
2…22 mA = -12.5%…112.5%, with error steps
0
1
1
0
4…22 mA = 0…106%, square root, with error steps
0
1
1
1
4…20 mA = 0…65,535, unsigned integer, with error steps
1
0
0
0
Not assigned
1
0
0
1
Not assigned
1
0
1
0
Not assigned
1
0
1
1
0…22 mA = A/D count, with fixed error
1
1
0
0
3.6…21 mA = NAMUR NE 43, with fixed error
1
1
0
1
3…21 mA = -6.25 to 106.25% with fixed error
1
1
1
0
2…22 mA = -12.5 to 112.5% with fixed error
1
1
1
1
Not assigned