Rockwell Automation 1794-IE8H, Series B FLEX I/O 8 Input Hart Analog Module Installation Instructions User Manual
Page 26

26 FLEX I/O 8 Input HART Analog Module
Publication
1794-IN108D-EN-P - January 2014
The extended configuration data table is accessed (read/write) by using a
MSG or CIO instruction. Refer to Field Descriptions on page 27 for more
information.
Error Level 0.1 mA Steps (Series A Mode)
Word
Bits
Description
Word 0
13
12
11
10
09
Error level channels 0...3
Word 1
13
12
11
10
09
Error level channels 4...7
0
0
0
0
0
Disabled
0.1 mA * binary valve = remote fault alarm
Examples
Data Format
2...22 mA
-12.5...112.5%
Binary value = 7, 0.1 mA * 7 = 0.7 mA
Remote fault alarm at -4.38% or +104.38%
Binary value = 15, 0.1 mA * 15 = 1.5 mA
Remote fault alarm at -9.38% or + 109.38%
Extended Configuration Data Table (Series A Mode)
Config
Word
Bits 15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
PMI
Ch 7
PMI
Ch
6
PMI
Ch
5
PMI
Ch
4
PMI
Ch
3
PMI
Ch
2
PMI
Ch
1
PMI
Ch
0
SM
E
Ch
7
SM
E
Ch
6
SM
E
Ch
5
SM
E
Ch
4
SM
E
Ch
3
SM
E
Ch
2
SM
E
Ch
1
SM
E
Ch
0
1
Reserved
HART Read Back
Threshold Ch 4...7
HS
LED
HS
Inht
50/
60
Hz
HART Read Back
Threshold Ch 0...3
Where Ch = channel
PMI = primary master inhibit
SME = secondary master enable
HS LED = HART status LEDs
HS Inht = HART status inhibit