20 ControlLogix ControlNet Bridge Module

Publication

1756-IN602A-EN-P - November 2005

Module Status Indicator and Display

The Module Status Indicator LED and Module Status Display provide
diagnostic information as summarized in the Diagnostics table.

Diagnostics

LED

Display

Cause

Recommended Action

Off

None

Module not communicating due
to a power supply fault or
internal fault.

1. Check the power supply.
2. Check the cable

connectors.

3. Make sure the module is

firmly seated in the
chassis.

4. If the indicator remains

off, replace the module.

Red

Msg

scrolls

(1)

Module’s network address is set
to 00, an invalid ControlNet
address. See footnote at end of
table.

1. (Optional, see page 9.)

Turn chassis power
supply off.

2. Remove the module from

the chassis.

3. Set the network address

switches to a unique
address (01 to 99).

4. Install the module in the

chassis.

5. If off, turn chassis power

supply on.

BPA#
ERR

Module detected a different slot
address from that latched when
you cycled power. Excessive
noise on the backplane causes
this error.

Replace the chassis or module.

BPRX
ERR

Too many CRC errors being
generated by the multicast
backplane receiver, so the
backplane multicast receivers
have been shut off.

Replace the module.

OK