24 ControlLogix ControlNet Bridge Module

Publication

1756-IN602A-EN-P - November 2005

Flashing
green/off

Temporary errors

None; unit will self-correct.

Node is not configured to go
online

Make sure the configuration
manager node is present and
working and selected address is
not greater than selected

UMAX

.

(1)

Flashing red/off

Media fault

Check media for broken cables,
loose connectors, or missing
terminators.

No other nodes present on
network

Add other nodes to the network.

Flashing
red/green

Incorrect network configuration

Cycle power or reset unit.

If fault persists, contact A-B
representative or distributor.

(1)

The configuration manager node is the node responsible for distributing ControlNet configuration data
to all nodes on the network.

Indicator States

Cause

Action