ControlLogix ControlNet Bridge Module 23

Publication

1756-IN602A-EN-P - November 2005

ControlNet Channel Status Indicators

The ControlNet channel status indicators appear in one of these
states:

• Steady - indicator is on continuously in the defined state.
• Alternating - the two indicators alternate between the two

defined states at the same time (applies to both indicators
viewed together). The two indicators are always in opposite
states, out of phase.

• Flashing - the indicator alternates between the two defined

states (applies to each indicator viewed independent of the
other). If both indicators are flashing, they must flash together,
in phase.

The Indicator States table summarizes the meanings of these states.

Indicator States

Cause

Action

Off

No power

None or apply power.

Steady red

Faulted unit

Cycle power or reset unit.

If fault persists, contact A-B
representative or distributor.

Alternating
red/green

Self-test

None.

Alternating
red/off

Incorrect node configuration

Check network address and other
ControlNet configuration
parameters.

Cause

Action

Off

Channel disabled

Program network for redundant
media, if required.

Steady green

Normal operation

None.