ControlLogix ControlNet Bridge Module 21

Publication

1756-IN602A-EN-P - November 2005

Red

BPIC

ERR

Hardware fault

within the module.

Replace the module.

CNIC

ERR

DUPL
NODE

The module’s network address is
the same as another module’s on
the link.

1. (Optional, see page 9.)

Turn off chassis power
supply.

2. Remove the module from

the chassis.

3. Set the network address

switches to a unique
address (01 to 99).

4. Install the module in the

chassis.

5. If off, turn chassis power

supply on.

RACK
ERR

Cannot read backplane EEPROM,
or rack/slot address incorrect

Replace the chassis.

Flashing
red

BOOT

Module has invalid firmware.

Update module firmware with
ControlFlash Update Utility.

ROM

UPDT

Flash update is in progress.

None required.

SNGL
KPR!

Module detected that it has
been connected to a ControlNet
1.0 or 1.25 (single-keeper)
network.

Update the firmware of module at
node address 01 and reschedule
the network.

Diagnostics

LED

Display

Cause

Recommended Action

OK