14 MicroLogix 1200 Programmable Controllers

Publication 1762-IN006C-EN-P - September 2009

Panel Mounting

Mount to panel using #8 or M4 screws. To install your controller using mounting screws:

1. Remove the mounting template from inside the back cover of this document.

2. Secure the template to the mounting surface. (Make sure your controller is spaced

properly. See Controller Spacing on page 12.)

3. Drill holes through the template.

4. Remove the mounting template.

5. Mount the controller.

6. Leave the protective debris strip

in place until you are finished
wiring the controller and any
other devices.

Connecting 1762 I/O Expansion Modules

Connect 1762 I/O after mounting the controller. Remove the expansion port cover to install
expansion I/O modules. Plug the ribbon cable connector into the bus connector. Replace the
cover as shown below.

ATTENTION

Remove power to the system before installing expansion I/O
or damage to the controller may result.