MicroLogix 1200 Programmable Controllers 23
Publication 1762-IN006C-EN-P - September 2009
Input Specifications
Description
1762-L24AWA, -L40AWA
1762-L24AWAR, -L40AWAR
1762-L24BWA, -L24BXB, -L40BWA, -L40BXB
1762-L24BWAR, -L24BXBR, -L40BWAR, -L40BXBR
Inputs 0 through 3
Inputs 4 and higher
On-State Voltage
Range
79 to 132V ac
14 to 24V dc
(+10% at 55°C/131°F)
(+25% at 30°C/86°F)
10 to 24V dc
(+10% at 55°C/131°F)
(+25% at 30°C/86°F)
Off-State Voltage
Range
0 to 20V ac
0 to 5V dc
Operating
Frequency
47 Hz to 63 Hz
0 Hz to 20 kHz
0 Hz to 1 kHz
(scan time dependent)
On-State Current:
• minimum
• nominal
• maximum
• 5.0 mA at 79V ac
• 12 mA at 120V ac
• 16.0 mA at 132V ac
• 2.5 mA at 14V dc
• 7.3 mA at 24V dc
• 12.0 mA at 30V dc
• 2.0 mA at 10V dc
• 8.9 mA at 24V dc
• 12.0 mA at 30V dc
Off-State Leakage
Current
2.5 mA max.
1.5 mA min.
Nominal
Impedance
12K
Ω at 50 Hz
10K
Ω at 60 Hz
3.3K
Ω
2.7K
Ω
Inrush Current
(max.) at 120V ac
250 mA
Not Applicable