Input specifications – Rockwell Automation 1762-Lxxxxx MicroLogix 1200 Programmable Controllers Installation Instructions User Manual

Page 23

Advertising
background image

MicroLogix 1200 Programmable Controllers 23

Publication 1762-IN006C-EN-P - September 2009

Input Specifications

Description

1762-L24AWA, -L40AWA
1762-L24AWAR, -L40AWAR

1762-L24BWA, -L24BXB, -L40BWA, -L40BXB
1762-L24BWAR, -L24BXBR, -L40BWAR, -L40BXBR

Inputs 0 through 3

Inputs 4 and higher

On-State Voltage
Range

79 to 132V ac

14 to 24V dc

(+10% at 55°C/131°F)
(+25% at 30°C/86°F)

10 to 24V dc

(+10% at 55°C/131°F)
(+25% at 30°C/86°F)

Off-State Voltage
Range

0 to 20V ac

0 to 5V dc

Operating
Frequency

47 Hz to 63 Hz

0 Hz to 20 kHz

0 Hz to 1 kHz
(scan time dependent)

On-State Current:

• minimum
• nominal
• maximum

• 5.0 mA at 79V ac
• 12 mA at 120V ac
• 16.0 mA at 132V ac

• 2.5 mA at 14V dc
• 7.3 mA at 24V dc
• 12.0 mA at 30V dc

• 2.0 mA at 10V dc
• 8.9 mA at 24V dc
• 12.0 mA at 30V dc

Off-State Leakage
Current

2.5 mA max.

1.5 mA min.

Nominal
Impedance

12K

Ω at 50 Hz

10K

Ω at 60 Hz

3.3K

Ω

2.7K

Ω

Inrush Current
(max.) at 120V ac

250 mA

Not Applicable

Advertising