MicroLogix 1200 Programmable Controllers 27

Publication 1762-IN006C-EN-P - September 2009

Description

1762-L24BWA, 1762-L40BWA, 1762-L24BWAR, 1762-L40BWAR

Power Supply Input to
Backplane Isolation

Verified by one of the following dielectric tests:1836V ac for 1 second or 2596V
dc for 1 second

265V ac Working Voltage (IEC Class 2 reinforced insulation)

Input Group to Backplane
Isolation and Input Group to
Input Group Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 second or
1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced insulation)

Output Group to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second

265V ac Working Voltage (IEC Class 2 reinforced insulation).

Output Group to Output
Group Isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second

265V ac Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2
reinforced insulation)

Description

1762-L24BXB, 1762-L40BXB, 1762-L24BXBR, 1762-L40BXBR

Input Group to Backplane
Isolation and Input Group to
Input Group Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 second or
1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced insulation)

FET Output Group to
Backplane Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 second or
1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced insulation)

Relay Output Group to
Backplane Isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second

265V ac Working Voltage (IEC Class 2 reinforced insulation).

Relay Output Group to Relay
Output Group and FET
Output Group Isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second

265V ac Working Voltage (basic insulation) 150V Working Voltage
(IEC Class 2 reinforced insulation)

Advertising