MicroLogix 1200 Programmable Controllers 17

Publication 1762-IN006C-EN-P - September 2009

Wire Requirements

Wiring Recommendation

When wiring without spade lugs, keep the finger-safe covers in place. Loosen the terminal
screw and route the wires through the opening in the finger-safe cover. Tighten the terminal
screw, making sure the pressure plate secures the wire.

Wire Type

Wire Size (2 wire maximum per terminal screw)

Solid

Cu-90°C (194°F)

#14 to #22 AWG

Stranded

Cu-90°C (194°F)

#16 to #22 AWG

Wiring torque = 0.791 Nm (7 in-lb) rated

ATTENTION

Be careful when stripping wires. Wire fragments that fall into
the controller could cause damage. Once wiring is complete,
be sure the controller is free of all metal fragments before
removing the protective debris strip. Failure to remove the
strip before operating can cause overheating.