24 MicroLogix 1200 Programmable Controllers

Publication 1762-IN006C-EN-P - September 2009

Output Specifications

General

Relay Contact Ratings

Description

1762

-L24AWA
-L24BWA
-L24AWAR
-L24BWAR

-L24BXB
-L24BXBR

-L40AWA
-L40BWA
-L40AWAR
-L40BWAR

-L40BXB
-L40BXBR

Relay and FET Outputs

Maximum Controlled Load

1440 VA

Maximum Continuous Current:

Current per Group Common

8A

7.5A

8A

8A

Current per Controller

at 150V max

30A or total of per-point loads, whichever is less

at 240V max

20A or total of per-point loads, whichever is less

Relay Outputs

Turn On Time/Turn Off Time

10 msec (minimum)

(1)

(1)

scan time dependent

Load Current

10 mA (minimum)

Maximum Volts

Amperes

Amperes
Continuous

Volt-Amperes

Make

Break

Make

Break

240V ac

7.5A

0.75A

2.5A

(2)

(2)

1.5A above 40°C.

1800 VA

180 VA

120V ac

15A

1.5A

2.5A

(2)

1800 VA

180 VA

125V dc

0.22A

(1)

(1)

For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied dc voltage. For example, 28 VA/48V dc = 0.58A. For dc voltage applications less than 14V, the make/break ratings
for relay contacts cannot exceed 2A.

1.0A

28 VA

24V dc

1.2A

(1)

2.0A